Southwest Research Institute

INVESTIGATION OF THE SURFACE BURNING CHARACTERISTICS OF A 6MM THICK MATERIAL BOARD PANEL MATERIAL ID: MINERAL BOARD

FINAL REPORT
Consisting of 5 Pages
SwRI® Project No.L 01.11810.01.122
Test Date: March 16, 2006
Report Date: April 13, 2006

Prepared for:
The Basement Tuxedo
7017 Americana Parkway
Reynoldsburg, OH 43068

Signature page

This report is for the information of the client. It may be used in its entirety for the purpose of securing product acceptance from duly constituted approval authorities. Thsi report shall not be reproduced except in full, without written approval of SwRI. Neither this report nor the name of the Institute shall be used in publicity or advertising.

INTRODUCTION

This report represents the results of an ASTM E84 test on a specimen submitted by the client, tested at Southwest Research Institutes (SwRI's) Department of Fire Technology, located in San Antonio, Texas. The test is conducted in accordance with the procedures outlined in ASTM E 84-05, "Standard Test Method for Surface Burning Characteristics of Building Materials" (NFPA 255, ANSLUL 723 and UBC 8-1).

This test method is applicable to exposed surfaces, such as ceilings or walls, provided that the material or assembly of materials, by its own structural quality or the manner in which it is tested and intended for use, is capable of supporting itself in position or being supported during the test period. The test is conducted with the material in the ceiling position.

The purpose of this test method is to determine the relative burning behavior of the material by observing the flame spread along the specimen. Flame Spread and Smoke Developed index are reported. However, there is not necessarily a relationship between the two measurements.

This standard should be used to measure and describe the response of materials, products, or assemblies to head and flame under controlled conditions and should not be used to describe or appraise the fire-hazard or fire-risk of materials, products, or assemblies under actual fire conditions. However, results of the test may be used as elements of a fire-hazard assessment or a fire-risk assessment which takes into account all the factors which are pertinent to an assessment of the fire hazard or fire risk of a particular end use.

Test specimens are conditioned as appropriate in an atmosphere maintained between 68 amd 78oF and 45 to 55% relative humidity. Immediately prior to the test, the specimen is mounted in the furnace with the side to be tested facing the test flame. Cement board is placed on the unexposed side of the specimen to protect the furnace lid assembly. Sometimes, because of the nature of the material undergoing testing, additional support (e.g. wire, wire and rods, rods, and/or bars) is used to ensure that the specimen will remain in position during the test. The use of supporting materials on the underside of the test specimen may lower the Flame Spread Index from that which might be obtained if the specimen could be tested without such support and the test results do not necessarily relate to indices obtained by testing materials without such support.

The flame front position and light obscuration are recorded throughout the 10-minute test and used to calculate the Flame Spread and Smoke Developed indices. The temperature at 23 ft is also recorded. The Flame Spread and Smoke Developed indices reported herein are relative to the results obtained for mineral fiber-reinforced cement board and select grade red oak (moisture content between 6 and 8%). The mineral fiber-reinforced cement board is the calibration material used to obtain 0 values for Flame Spread and Smoke; red oak decks are used to obtain 100 values for Flame Spread and Smoke.

The results apply specifically to the specimens tested, in the manner tested, and not to the entire production of these or similar materials, nor to the performance when in combination with other materials.

Two model building codes (2003 International Building Code®, Chapter 8 Interior Finishes, Section 803 Wall and Ceiling Finishes, NFPA 5000, Chapter 10 Interior Finish, Section 10.3 Interior Wall or Ceiling Finish Testing and Classification) classify materials based on the Flame Spread and Smoke Developed indices. For reference purposes, the classification criteria are listed below:

ClassificationFrame Spread IndexSmoke Developed Index
A0-250-450
B26-750-450
C76-2000-450


ASTM E 84-05 REPORT CLIENT: The Basement Tuxedo SWRI PROJECT NO.: 01.11810.01.122 TEST DATE: MARCH 16, 2006 DAILY TEST NO:: 1
TEST RESULTS (ROUNDED TO NEAREST 5)
FLAME SPREAD INDEX (FSI): 0
SMOKE DEVELOPED INDEX (SDI): 15
TEST DATA
UNROUNDED FSI:1.8
UNROUNDED SDI:15.3
FSI TIME AREA (Ft*Min):3.6
SMOKE AREA (%*Min): 16.6
FUEL AREA (oF*Min):4942.0
OBSERVATIONS DURING TEST
IGNITION TIME (Min:Sec): 4:32
MAXIMUM FLAME FRONT DISTANCE (Ft.):0.5
TIME TO MAXIMUM ADVANCE (Min:Rec):6:12
MAXIMUM TEMP> AT EXPOSED TC (oF):545
TIME TO MAXIMUM TEMP (Min:Sec):9:24
TOTAL FUEL BURNED (Cu.Ft.):52.0
DRIPPING (Min:Sec):None
FLAMING ON FLOOR (Min:Sec):None
AFTER FLAME TOP (Min:Sec):None
AFTERFLAME FLOOR (Min:Sec(:None
CALIBRATION DATA (LAST RED OAK)
RED OAK SMOKE AREA (%*Min):102.8
RED OAK FUEL AREA (oF*Min):8415.8
GRC BOARD FUEL AREA (oF*Min):5261.4
ASTM E 84-05 REPORT

CLIENT: The Basement Tuxedo
SWRI PROJECT NO.: 01.11810.01.122
TEST DATE: MARCH 16, 2006
DAILY TEST NO:: 1